We can not test 21st century IEDs with 20th century testing technology.

Author:
Alex Apostolov, USA

INTRODUCTION

As we can see from the History articles in the magazine, different forms of protection have been used in electric power systems for more than a century. With the increase in the importance of protection, it has been necessary to ensure that the relays are able to perform their functions as expected, when necessary, and do not operate when not required. Throughout the years different testing tools have been used successfully with electromechanical, solid-state and microprocessor based relays. Protection engineers and testing specialists from around the world have developed confidence in traditional methods such as “constant current” or “constant voltage” that have served them well for over a century. These methods were more or less the things you could do with the test devices available through most of the twentieth century:

  • Fix the current at a specific level and then start reducing the voltage until the relay operates.
  • Fix the voltage and increase the current.

This works great with electromechanical relays, but unfortunately does not help us if we need to test advanced protection IEDs. This brings us to the issue of Questions.

As with any human activity, before we start, it is important first to ask ourselves some questions that will help us do a better job, i.e. not only to get the job done, but also to do it in the most efficient way possible.

Why are we testing?

This is the first question that we should ask. The reason is, because the requirements for testing can be very different, for example if a manufacturer is performing type testing of a new relay or a user is considering the acceptance of a multifunctional protection device, a certain set of things will need to be tested:

  • Characteristics of every function
  • Performance of different functions under various operating conditions
  • Performance of different functions under various non-operating conditions

These tests can be performed also with settings of the tested functions within the whole available range. There is a significant difference if we are testing a multifunctional protection IED during commissioning. In this case it will be sufficient to do testing only of the used functions with their application specific settings. Testing of the complete characteristic is not necessary. Checking of a couple of points just to ensure that the relay has the right settings and the wiring between the test switch and the relay is correct, is sufficient.

Things get more interesting when we are testing substation automation systems. There is a difference in the requirements, methods and tools if we are doing factory acceptance testing versus site acceptance testing.

What are we testing?

This second question has a lot to do with the complexity of the new world of protection, automation and control. And there are different answers to it. The requirements for testing tools and methods will depend on what we are testing:

  • Electromechanical relay
  • Multifunctional IED
  • Distributed protection scheme
  • Substation Automation System
  • Communications based protection scheme in the lab
  • Communications based protection scheme in the field

If we look at some of the examples above, testing of an electromechanical relay can be performed using a “constant current” or “constant voltage”, while the testing of an advanced multifunctional IED may require the use of electromagnetic transient simulation.

How are we testing?

This third question is related to the selection of the testing tools. It is clear that we can not answer it if we don’t already have the answers to the first two questions. But this is not sufficient. We need to also know very well the capabilities of the test equipment available, as well as the functionality of the available testing tools.

For example, if we are testing a high-burden electromechanical ground overcurrent protection relay, we will need to use a test set that can deliver the required current at the necessary compliance voltage. But if we are testing a relay using the IEC 61850 sampled values and GOOSE messages – a test device with communications only capabilities and support of the protocol may be used. Manual testing may be OK if we are just verifying the connections of a relay during commissioning, while execution of large, object-oriented test plans is needed for acceptance testing.

We will try to explain in mode details the answers to the above questions and discuss some modern methods and tools that can be used for twenty first century testing.

Quality assurance process

The requirements for testing that can be defined by a quality assurance process used by a manufacturer, utility or anyone else, can vary significantly from one entity to another and depend on philosophy, experience, available tools and other factors. One of the benefits from the introduction of IEC 61850 is that it not only defines a new communications protocol, but also describes in Part 4 of the standard a quality assurance process that can be applied for any device or system, not only to the ones supporting the standard.

The quality assurance is a process that requires involvement of all participants in the development and manufacturing of individual devices and their acceptance by the user, engineering, integration, commissioning and maintenance of a substation protection, automation and control system (SPACS). Each party –manufacturer, integrator and customer – has a different role in the process that has to be clearly defined for every stage of a project.

As can be seen from Figure 1, the manufacturer is responsible for the development of devices according to ISO 9001, type testing and system testing of all IEDs that can be integrated in a SPACS. After a product is made available on the market, a vendor still needs to perform regularly, specific tests to ensure the quality of the products delivered to customers.

Once a product is available on the market, the user makes a decision if it can be applied in the system using acceptance testing. In principle, acceptance testing is similar to type testing – it is used to prove that the IED performs as stated in its technical specification. What is included in the testing is based on the acceptance criteria of the user. It may cover every function in the tested device, but at least all features to be used should be tested. In the case of microprocessor based relays, this is the time when the user should test the full characteristics – distance, inverse-time overcurrent, etc. This is because digital algorithms do not deteriorate with time. Once we know that the characteristics are within the stated tolerances, we do not need to check the full characteristic, just a few points to make sure that the wiring and settings are OK. Once a device is accepted for use in an electric power system, we need to make sure that it can operate within a SPACS. This requires interoperability and integration testing.

Factory and site acceptance testing play a key role in ensuring that the system will operate correctly under all possible conditions. The system hierarchy and distribution of functions between multiple devices require the use of new methods and tools that become more complex when communications are used for exchange of signals between the individual devices.

It is very important to understand that the definition of test procedures, methods and tools should be part of the design of the system. The description of the functionality of a protection, automation and control scheme should come with a specification of the tests to be performed to verify that it performs as designed. Once the SPACS is in service, we need to make sure that all components of the system are operating properly at any moment in time. The quality of IED based systems can be ensured successfully using the advanced monitoring tools that are built into most of these devices. Analysis of the monitoring functions can help the user determine which components’ states are not know in order to define the requirements for maintenance related testing. Once we understand the quality assurance process, we can start looking into how it can be implemented. This is easier to achieve by using a specific example – multifunctional transmission line protection.

Transmission Line Protection Functions

We can start our analysis by looking into what we are testing. The main purpose of any multifunctional distance protection IED is to detect and clear as quickly as possible short circuit faults that can damage substation equipment or create conditions that adversely affect system stability or sensitive loads. This is achieved through the use of instantaneous distance elements or communications based protection schemes.

The distance elements can be simple or complex, with different operating characteristics, with or without directional supervision. The functions in the transmission line protection relay have a hierarchy that needs to be considered for the testing of the device (Figure 2). The IED actually works with an image of the electric power system currents and voltages provided through several conversions – the instrument transformers and secondary circuits in the substation, as well as the analog inputs and internal processing in the device. The secondary currents and voltages that are applied to the distance protection relay are filtered and processed in the analog input module and provide instantaneous sampled values to the internal digital data bus of the IED. These sampled values are used to calculate various measurements (e.g. current and voltage phasors or superimposed components) used by the different protection functions. The outputs of the measurement elements become inputs to protection or other functional elements of the device. Each basic protection element operates based on a specific measured value – phase or sequence current, voltage, frequency, etc. Measurements of active, reactive and apparent power or power factor are often available from the relays if required in the substation automation system.

When a protection element detects an abnormal condition, it may operate and issue a trip command to clear a fault. It may also interact with other protection elements in a distance protection scheme used for acceleration or adaptation of the relay to changing configuration or system conditions.

The multifunctional distance protection relays also perform automatic functions such as multi-shot reclosing and local backup protection such as breaker failure protection.

The successful detection and clearing of any abnormal system condition is affected not only by the correct configuration and operation of the protection elements, but it also needs healthy secondary current and voltage circuits, as well as breaker trip or close circuits. This requires the relays to also perform monitoring functions, such as trip circuit supervision, current and voltage circuit supervision or different breaker monitoring functions.

Last, but not least, the relays are also used as the first level in the hierarchy of a substation automation system, event recording and analysis functions. Based on the pre-fault and fault currents and voltages they calculate the location of the fault, magnitude and angle of the currents and voltages before and after the fault, duration of the fault and other parameters.

The interaction of different logical and functional elements needs to be well understood, since there are differences between the implementation of some protection functions in electromechanical and microprocessor based relays. For example, a directional ground overcurrent protection in a microprocessor-based relay is achieved as a combination of overcurrent and directional elements.

 

 

Advanced functions

The technology for protection of transmission lines has changed significantly in the last two decades due to the advancements of microprocessor based hardware and new algorithms implemented in the relay software. We can not cover a lot in this article due to the limited space, so we will just use as an example some protection or protection related functions based on superimposed components - fault, directional and power swing detection, as well as faulted phase selection.

When a fault, such as a short circuit, occurs in the electric power system, it leads to a dynamic transition from the normal system condition to a fault system condition. The currents and voltages measured by the relay will change as a function of the pre-fault system configuration and the parameters of the fault - fault type, fault location, fault resistance, etc.

Superimposed components can be used for system analysis if the fault system condition is caused by a single event (the fault inception) and no other simultaneous event has occurred. In this case the faulted network state can be considered as the result of the superposition of the pre-fault and the fault generated quantities (Figure 3).      

There are different approaches to the derivation of the superimposed components. The general aim is to estimate what the expected no-fault current or voltage sample should be at this moment and then subtract that from the latest sample captured.

Once the superimposed components of the currents and voltages have been calculated, the relay can run in parallel the different functions based on these quantities:

  • Fault detection
  • Faulted phase selection
  • Directional detection
  • Power swing detection

 

Testing Requirements

Understanding the algorithms of the devices we are testing answers the question what we are testing. This can be used to determine how we are going to perform the tests. Conventional methods for testing of the main functions in transmission line protection relays – the distance and the directional – have been used for many years based on the requirements for testing of electromechanical or solid state relays. They are also influenced by the technology available at the time. As a result the Constant Current and Constant Voltage methods are the ones usually applied. The main characteristic of these methods is that one of the parameters is fixed at a pre-selected value, and then the second parameter is changed until an operation of the tested elements is detected.

From the description of the superimposed components based functions in transmission line protection relays, it is clear that using these methods is not going to work for the testing of such devices. This is due to the simple fact that the relays are designed to detect faults in real life conditions, i.e. when there is simultaneous change in the magnitude and angle of both the faulted phases currents and voltages.

The requirements for testing of such advanced functions clearly point towards dynamic testing. We still need to be careful with regard to the understanding of this term. In some cases a state change from pre-fault to fault condition may be sufficient. However, if this is represented as a step change in the fault injection to the distance relay under test, it still may result in an operating time slower than expected due to the fact that the current waveform is not realistic. That is why electromagnetic transient simulation is the best way to generate the signals used for the testing of the distance element.

Testing of Multifunctional distance protection relays

When we analyze the complexity of modern multifunctional distance protection devices, it is clear that their testing requires the use of advanced tools and software that can simulate the different system conditions and status of primary substation equipment and other multifunctional IEDs. The test system should be able to replay COMTRADE files from disturbance recorders or produced from electromagnetic transient analysis programs. It should be able to apply user defined current and voltage signals with settable phase angles, as well as execute a sequence of pre-defined pre-fault, fault and post-fault steps.

The testing of the different IED elements has to start from the bottom of the functional hierarchy and end with the most complex logic schemes implemented in the device.

Protective relays with such schemes operate based on the state of multiple monitored signals such as permissive or blocking signals, breaker status signals, and relay status signals. Time coordination of these signals and synchronization with the pre-fault and fault analog signals is required in order to perform adequate testing of these types of schemes. The test device needs to be able to properly simulate the distance protection environment from Figure 2, as well as to monitor the operation of the relay under the simulated conditions.

Testing of the analog signal processing and measurement functions

The analog signal processing is the first critical step in the testing of a transmission line protection relay because if any problems exist at this level, they will be reflected at any other step up the functional hierarchy. The only problem is that the data bus of the IED is usually not directly accessible or visible through the relay communications or user interface. That is why an indirect method is recommended. If we configure the testing software to generate pure sinusoidal waveforms of balanced currents and voltages with their nominal values and no phase shift (zero degrees) between the currents and voltages in the same phases, and record the applied waveforms with the tested relay, extracting and analyzing the records will allow us to evaluate if there is any problem with the analog signal processing and recording functions.

The testing of the measurement functions of the relay is the next step. It can use the same setup as described above, at least as the initial measurements test condition. The measured phase currents and voltages in this case need to be as close as possible to the nominal balanced values applied to the relay by the test device (within the accuracy range specified by the relay manufacturer). The positive sequence measurements should be within tolerance of the phase values. Since the applied phase currents and voltages are balanced, the measured negative and zero sequence values should be close to zero (again within the expected tolerance range).

Testing of the main protection functions

When testing the individual protection elements in a conventional fashion, it is very important that they are the only enabled protection function (if all protection elements share the same relay output). If the IED has multiple relay outputs and different protection elements are mapped to different outputs, we need to make sure that the test device monitors the correct relay output during the test.

For a modern test system, such mappings shouldn’t be necessary. A good fault model will correctly generate a system condition that the relay should distinguish, indicate, and trip correctly for based on the enabled protection element characteristic.

If we (based on the measurement functions tests) assume that the relay measures accurately the applied current and voltage signals, the testing of the distance elements should give us an indication of what is the characteristic of the tested zone and expected relay operating time when the apparent impedance seen by the distance element based on the applied currents and voltages is within the operating characteristic.

Constant voltage and constant current methods may be used for the distance characteristics testing. This is acceptable for some microprocessor based relays that use distance elements based on the relationship of current and voltage phasors. While such tests are related to checking the distance characteristic of the relay, they may not be suitable for the testing of the relay tripping time. This is especially important for Zone 1. If the relay uses superimposed components for the fault detection, faulted phase selection or directional detection, the ramping of the current or voltage in some of the conventional test methods is not going to be seen as a fault condition and the relay under test is not going to operate. Electromagnetic transient simulation is the best way to generate the signals used for the performance testing of the distance element. Evaluation of the distance element operation for multiple points on the selected characteristic is typically required. Figure 7 shows the configuration for the testing of a distance relay with a complex characteristic.

If the results from the testing of the distance characteristics and the operating time are within the expected range, the next step is the testing of the different communications based schemes.

Testing Of Distance Protection Schemes

The testing of distance protection schemes is the final step in the testing of a distance relay and is based on the assumption that all individual protection elements – distance, overcurrent, directional, faulted phase selection, etc. have already been tested and proven to be operating correctly. An important consideration is the purpose of the test. If the test of a distance scheme is performed as part of a relay acceptance test, the complete test can be performed by the simulation of the analog and binary signals that the relay is going to measure or monitor under the specific test case conditions. However, if the test is part of the commissioning of the protection system of a transmission line before it is put in service, it may be necessary to test the complete protection system, including the communications channel. End-to-end testing using GPS synchronization is the preferred method in this case.

When communication aided schemes are used in complex system configurations, including double circuit transmission line or transmission line loops with or without mutual coupling, sequential tripping of faults on adjacent lines may result in incorrect operation of the accelerated schemes. It is required to develop test sequences simulating such conditions to verify that the protective relay is going to operate correctly.

The next step in the Distance Protection Scheme testing is the extension of the same test cases into the full operational protection system test. This is commonly referred to as End-to-End Testing or System Testing.

IEC 61850 can also be an integrated function in transmission line protection relays. It impacts the testing process by requiring the test system to be configurable using the Substation Configuration Language, as well as to be able to simulate GOOSE and sampled values, as well as to subscribe to and process GOOSE messages from the tested relay.

Transient simulation based testing

When we analyze the complexity of modern multifunctional distance protection devices, it is clear that their testing requires the use of advanced tools that can simulate the different system conditions and status of primary substation equipment and other multifunctional devices. The test system should be able to replay COMTRADE files from disturbance recorders or produced from electromagnetic transient analysis programs. The focus at this time is determining the performance of the device under realistic system conditions as required by the application. If necessary, the test cases should also include synchronous or asynchronous out of step conditions simulation to test the power swing blocking or tripping functions. Performance of the tested relay when a fault occurs during a power swing should also be included in the test plan.

The testing tools should allow easy configuration and execution of such transient simulations as part of the testing process, as well as proper evaluation and reporting of the operation of the tested device (Figure 6).

The protection of double circuit or other parallel line configurations need to be able to operate under different system conditions, evolving and cross-country faults, sequential tripping conditions and under the influence of mutual coupling. All of the above needs to be considered in the testing of such protection relays or communications based schemes.

If we are testing a relay used on a double circuit line, it is important to properly model not only the impedances of the two circuits, but also the mutual coupling between them. Generic programs such as EMTP or ATP can be used to produce such files. They require good knowledge of the software and proper configuration of the model and simulation. Specialized testing tools make this easier by providing a template for the transient simulation of different fault conditions on mutually coupled double circuit line (Figure 6).

This offers significant advantages over the testing based on a sequence of steps programmed in the software by manually entering voltage and current phasors calculated by a steady state fault analysis software which do not properly simulate the dynamic transition from one state to another.

PDF Version

Ad: Navigate the Sea of Data
Ad: GE Multilin's 3 series - Fast, accurate & flexible protection
Ad: ABB Relion®. The perfect choice for every application.