Authors: Boris Bastigkeit, Thomas Schossig and Dr. Fred Steinhauser, OMICRON electronics, Austria
The reliability of electricity generation, transmission and distribution is directly related to the reliability and quality of the protection system. Regardless of which generation of protection equipment is protecting the elements of the system, it is always necessary to prove its proper functioning during commissioning, and after certain duration of service. Complex technical devices and protection equipment can fail for any reason therefore 100% security is impossible. While electromechanical relays have problems with ageing mechanisms and coils, static relays deal with drifting analog circuits and digital relays struggle with software bugs and firmware updates. Due to the inactive nature of relays during proper network conditions, a possible relay malfunction can only be detected at the instant of a power system fault.
Thus, due to the vital role protection relays play to achieve high power system stability and also in preventing the power system owner from high financial losses due to damaged power system elements, the risk of malfunctioning relays should be minimized. Thorough commissioning and routine testing of relays should be undertaken to minimize this risk. On the other hand, trends like liberalization of the electricity market and privatization of utilities put the relay commissioning, routine testing and protection engineering departments under pressure to save costs.
How can the quality of the protection system and as a direct result, the power system, be sustained or even improved when the staff for relay evaluation, commissioning and routine testing is generally reducing? One way to escape this dilemma is to increase the productivity of the remaining experts through automation. Automation can save the relay experts’ time, allowing them to concentrate on solving and analyzing actual failures during power system operation, or relay commissioning and maintenance. Furthermore automation can even increase the depth of testing in a shorter time, raising not only the efficiency but also the quality. This article describes testing of modern relays and the impact of IEC 61850 on protection testing in a practical manner.
Challenges for today's protection engineers
One of the biggest current challenges today's protection engineers have to deal with is to master the high complexity of modern protection systems. Further challenges which are faced by engineers ( e.g. operating the systems closer to the limit, distributed generation, rising time and cost pressure etc.) will not be discussed here in detail.
Reasons for the risen complexity of modern protection devices: In order to master the field of protection engineering, one needs solid expertise and broad theoretical basics on electrical power systems. Thus the field per se is complex. The following points will show where the additional complexity of modern protection devices originates:
Multifunctional protection relays: Whereas formerly there was mostly one protection function implemented per device, nowadays prevail multifunctional protection devices. Even though the multifuncionality is not used to the full extent most of the time, it is still there and thus increases complexity.
Integration of additional functions: Transient recorder, SCADA functions, interfaces, process bus, fault locator, control functions, plc functionality, phasor measurements functions and many further functions are integrated into protection devices nowadays. The standard IEC 61850 stays abreast of this development and emphasizes it by using the term "IED" (Intelligent Electronic Device) instead of calling them protection devices.
Algorithms are handled in the software (firmware): This fact results in a higher complexity, because of requirements for frequent firmware updates.
PC- Software: Modern protection devices are parametrized and read out by PC-software. Therefore one faces not only the advantages but also the problems resulting from PC usage. Only some of them are: short life cycle of the PC hardware and pc operating systems, error proneness, networking problems with the corresponding security, firewalls, driver, interface and updates issues, the classic SW bugs, different SW concepts of different vendors, etc..
Life cycle of protection devices becomes shorter: New ideas and concepts as well as rapidly developing fundamental technologies are the basis for innovations, which enter the products within increasingly shorter cycles. As a result the knowledge gained about such devices with short life cycle will also pay off for a short time.
Greater variety of interfaces: Formally one could do everything with the classical 1A/5A and 100V/110V interfaces and some contacts. Nowadays this has changed completely. In addition to the "classical" interfaces there are interfaces to the SCADA system e.g. IEC 60870-103, Modbus, DNP, IEC 61850. For the process bus we use IEC 61850 GOOSE, non conventional VTs and Cts with low level or data interfaces like IEC 61850 Sampled Values are available. Time synchronization, communication between the protection devices (e.g. line differential protection), proprietary communication interfaces to the PC, or station computer etc. are further interfaces that have to be dealt with.
As a central result of all of these points we can see a very high amount of parameters available in modern protection devices. Finding strategies to manage all these parameters becomes more and more important.
Ways to manage the big amount of parameters
In most cases only a very small amount of parameters is actually set to configure the relay to protect certain equipment. Therefore utilities for a common application such as line protection often define a standard setting for a standard application. This standard setting often is defined in connection with the acceptance test by the standardization group of the utility. This standardization work is usually done in the laboratory of the utility. The field engineers who then apply the relays to the local conditions do not touch the standardized parameters anymore. Only a very limited amount of relevant parameters is varied, thus reducing the complexity.
Often the standardization process inside the utility does not stop there. Many utilities have started to create standard test plans in connection with the settings´ standardization process. These standard test plans are handed over to the field engineers together with the standard settings.
Relay Test Automation
The last section of this article highlights that standardization is the key strategy to dealing with the challenges protection engineers in today's utilities are facing. Once the utility has standardized on a few relay types and its basic parameterization, a next natural step is to create standardized test plans that help the engineer to verify the IEDs functionality in a standardized manner. "Test automation" in this regard does not mean to create a fully automated procedure that runs through after a single button click. Well, it can be. However, the focus is more on creating a standardized procedure that verifies in predefined and standardized comprehensible test portions - step by step - all the important functionalities of the IED under test.
Testing an IED shall assure that its designated (protective) function is fulfilled. Before putting together test strategies, possible reasons for relay malfunctions should be considered:
Modern IEDs present many hurdles for test automation:
General rules for successful test automation programs:
The listed aspects lead to the creation of guidelines which should be observed when creating standardized test templates:
1. A relay has to be tested to its actual settings. Testing a relay to factory default settings or other changed settings does not guarantee a proper function with actual settings. -> Automatic test plans (Fig.1) have a possibility to adapt to fit the actual relay settings. E.g. by linking the test steps to the relay settings.
2. The person in charge should understand all aspects of the test plan and should be able to adapt the test plan if necessary -> Tools for creating a test plan should be easy to use in such a way that no programming is required to build or change it. Ideally the test plan is built by adding/ adapting standard test functions (test modules) that can easily be linked to the actual settings of the protection.
3. Blocking/disabling of overlapping functions for testing purposes should not be done, because the unblocking/enabling can be forgotten after the test. Secondly the influence the parallel functions may have on each other (e.g. limited processing power) is not tested. -> The test software must support test algorithms that allow stimulation of exactly the function under test although the other functions are active in parallel (Fig. 2).
4. GOOSE possibilities: The GOOSE can be used for transmission of any kind of data (startup, trip, measuring values, counters). This offers new possibilities for protection itself and its testing. Due to GOOSE's multicast mechanism distribution every information is available everywhere- in every feeder for instance. Distributed functionalities can be realized without additional effort for wiring etc. -> Utilizing GOOSE messages for testing purposes allows reducing the complexity of test plans. The complexity of test plans can be reduced if efficient testing is considered in the engineering phase for the protection IEDs already.
5. Testing of relays should be done against the settings calculated in the relay setting sheet. Reading the settings file directly from the relay and testing against those settings introduces the danger of (human) errors when setting the relay or unwanted re-parameterizations, for whatever reasons, are not discovered. -> Testing against the settings read directly from the relay is not covering an important error source (Fig. 3).
6. As it is possible to freely program the logic of modern digital relays, it is required that the tester can easily add new tests to a standard test plan for those "non standard" functions. ->Adaptation of standard test plans has to be easily possible.
7. Automatic assessment of test results, according to given relay tolerances, is a must. However, the automatic assessment can never fully replace the plausibility check of the results by the testing relay expert. -> Visualization and straight forward graphical representation of the results is necessary to allow the expert a quick and easy plausibility check of the test results (Fig. 4).
8. Utilization of easy to use network simulation tools helps to do a plausibility check if the protection IEDs basic settings are correct. This way errors in calculating the IED parameters or setting errors can be discovered. -> Ideally the test plan contains test steps that simulate faults in a network model that is based on the primary data of the protected network components (Fig. 5).
9. Once a failure is found in a relay, be it the relay itself, a wrong setting or even a wrong test plan, it is important to have the appropriate analysis tools and support to quickly locate and eliminate the error source. -> Automated testing requires very good documentation and visualization with event recordings and graphics of all the test steps. The test set should provide troubleshooting tools like transient recording, wiring checking tools and measurement functions (Fig. 6).
Generating Fault Quantities
It is the task of an IED (especially for protection purposes) to detect faults on assets. To do this the IED receives information regarding the developing of values as current, voltage, phase shift… For testing these values can be provided in different manners.
Conventional measuring transformers: As mentioned the 1A/5A and 100V/110V is a well established interface for a long time already. Due to that test sets are available and approved. Combined with powerful software a test even of complicated protection functions is possible.
Distributed functions (as busbar protection) especially with different nominal values of the CTs, require test sets with high power and high amplitudes of currents.
Non-Conventional Measuring Transformers: Non conventional transformers such as Rogowski coils and optical CTs, solve some known problems of conventional transformers - for example CT saturation. A disadvantage might be non standardized interfaces and protocols used, that can make them difficult to test. Sampled Values as described in the next paragraph might accelerate the use of this technology. In the cases when non-conventional instrument transformers are used, Sampled Values primary injection is accepted as a trustworthy test.
Sampled Values : IEC 61850-9-2 describes a special mapping to transmit measuring values as primary values on Ethernet, they are called "Sampled Measured Values" or "Sampled Values" (SV). A special guideline ("9- 2LE"defines a certain profile of this standard with dataset (what are the values to be transmittedvoltages and currents) and sample rate (80 samples per cycle for protection and measurement, 256 for Power Quality purposes) and enables an easy implementation for vendors and users. So called Merging Units (MUs) produce the SV streams. If the standard does not describe a special technology to make sampled values out of "real" values these MUs can be utilized for output of non-conventional transformers or conventional transformers and can even be a part of the transformer itself.
Primary Injection: For a plausibility check and even for "real" protection testing, primary injection will become more and more important. If in case of SV the measuring values are "just a stream of primary values" the proper functionality of an MU can be easily tested in that case. For testing the verisimilitude a powerful "secondary injection test set" is sufficient.
Advanced Testing Background: IEC 61850 utilizes different possibilities of communication. For client/server communication and exchange of non time critical information between a substation HMI (client) and an IED (server) services such as reporting, logging and control are used. On the other hand the standard describes a set of "real time services" for fast exchange of data such as the mentioned GOOSE and Sampled Values. For this "real time data" a conventional client-server communication is not sufficient and an unconfirmed mechanism is used - a multicast that spreads out information over a network.
Protection Testing in that case involves the measurement of the performance of the overall transfer time as described in IEC 61850-5.
The standard describes several performance classes. For important information as "trip" the overall transmission time shall be less than 3 ms This requires the testing of the overall system.
GOOSE Performance : Occasionally there are reports about failed GOOSE applications due to insufficient GOOSE performance. In some places this has even raised doubts about the usability of GOOSE in general. Most of these problems emerge from non-recommended usage or from an improper analysis of the applicability of devices. One problem is the lack of performance specifications, which would facilitate the assessment of a device in a distinct application.
Measuring GOOSE performance is indeed a challenge. IEC 61850-10 lays out some testing methodology for the communication latency in clause 7.2, but it makes some assumptions about access points which are often hard to meet. Ideally, test terminals which are immediately operated at the transition of a message between the protocol layer and the application would have to be used, but this option is only available to the device vendor. If normal physical outputs are used, they should have no essential delay (e.g. solid state types), the delay of a normal contact may be larger than the latencies to be measured. And finally, there are devices that may have no physical outputs at all.
The user can only make more or less indirect measurements. Some useful specifications to help the system integrator to better assess a device, can be derived. The idea is to measure a round-trip time to obtain a conservative estimate for the GOOSE performance. A GOOSE is sent out from a test set (TS) to a device under test (DUT), which sends a GOOSE back to the test set as fast as possible. Figure 9 shows what times are involved and make up the round-trip time measured by the test application.
To make this method work, a number of assumptions must be made:
IEC 61850-10 already requires applying statistical methods, with average values and standard deviations computed from at least 1000 measurements. This statement contains another assumption, since it implies that the measured values conform to a normal distribution. The assumption allows the use of established mathematical methods for processing the results. Even if the kind of distribution is hard to determine beforehand, using this model shows to be a conservative approach. This will be mentioned again below. The statistical evaluation of a sufficient number of round-trip times delivers an average value and a standard deviation, which is composed of the characteristics of the DUT and the test set (see figure 8). To calculate the figures of the DUT, the performance figures of the test set need to be known. To obtain these figures, the round-trip test is performed with another, identical test set as DUT.
With modern test automation tools providing scripting features, the task of repeated measurement and continuous calculation of the statistical parameters can be easily performed. For a data sheet, a rating such as a worst case figure is needed as a specification. An upper limit can be derived from the confidence interval for the communication latency and used as a maximum rating for characterizing the GOOSE performance of a device.
With high performance test sets, values of well below 1ms for 99.99% confidence are achievable. So just one out of ten thousand values would theoretically exceed this rating. In fact, a closer look at the results reveals that the test set performance is even better determined in the distinct case. In a series of more than 250,000 repetitions, not a single measurement showed a value greater than the upper limit for a 99% confidence interval. Thus, a normal distribution would have resulted in thousands of outliers. The actual distribution is obviously more reliably clustered around the average value than a normal distribution, having an upper limit and not showing tails of the distribution extending into infinity.